ADAM-6260
6-ch Relay Output Modbus TCP Module- 6-ch Relay Output, 2-port Ethernet
- Daisy chain connection with auto-bypass protection
- Remote monitoring and control with mobile devices
- Group configuration capability for multiple module setup
- Flexible user-defined Modbus address
- Intelligent control ability by Peer-to-Peer and GCL function
- Multiple protocol support: Modbus TCP, TCP/IP, UDP, HTTP, DHCP
- Web language support: XML, HTML 5, Java Script
Indent
Get Quote
Introduction
In order to fulfill ideal remote DAQ devices in IoT world, Advantech releases ADAM-6200 series, a new selection of Ethernet I/O family comprised of analog I/O, digital I/O and relay modules. ADAM-6200 series module possesses plenty of advanced features whatever the evolution of hardware design and what’s worth expecting for user is a variety of useful software functions to make it effective in the application field. With new design and strong capabilities, ADAM-6200 can be a well-integrated I/O solution in Ethernet control system
Specification
ADAM-6260-AE | ||
---|---|---|
Digital Input | Input Voltage | Dry contact: Logic level 0: close to GND Logic level 1: open Wet contact: Logic level 0: 0~3 VDC Logic level 1: 10~30 VDC |
Counter Input | 3kHz (32 bit + 1 bit overflow) | |
Dry Contact | Logic 0: Open, Logic 1: Closed to DI COM | |
Frequency Input Range | 0.1 ~ 3kHz | |
Input Impedance | 5.2 kW (Wet Contact) | |
Keep/Discard Counter Value when power off | – | |
Supports Inverted DI Status | – | |
Transition Time | 0.2 ms | |
Wet Contact | Logic 0: 0 ~ 3 VDC or 0 ~ -3 VDC, Logic 1: 10 ~ 30 VDC or -10 ~ -30 VDC, (Dry/Wet Contact decided by Switch) | |
Environment | Humidity (Operating) | 20 ~ 95% RH (non-condensing) |
Operating Temperature | -10 ~ 70°C (14 ~ 158°F) | |
Storage Humidity | 0 ~ 95% RH (non-condensing) | |
Storage Temperature | -20 ~ 80°C (-4 ~ 176°F) | |
General | Connector | Plug-in 5P/15P screw terminal blocks |
Dimensions | 110 x 60 x 27 mm | |
Ethernet | 2-port 10/100 Base-TX (for Daisy Chain) | |
LED Indicators | 6 RL | |
Power Consumption | 4.5 W @ 24 VDC | |
Power Input | 10 – 30 VDC (24 VDC standard) | |
Protection | Built-in TVS/ESD protection, Power Reversal protection, Over Voltage protection: +/- 35VDC, Isolation protection: 2500 VDC | |
Protocol | Modbus/TCP, TCP/IP, UDP, HTTP, DHCP | |
Watchdog Timer | System (1.6 second) & Communication (programmable) | |
Relay Output | Breakdown Voltage | 500 VAC (50/60Hz) |
Channels | 5 Form C and 1 Form A | |
Contact Rating | 250 VAC @ 5A 30 VDC @ 5A | |
Frequency of Operation | 360 operations/hour with load, 72,000 operations/hour without load | |
Insulation Resistance | > 10 GΩ @ 500 VDC | |
Isolation between Contact | 1000 Vrms | |
Max. Breakdown Capacity | 1250 VA | |
Max. Switching Voltage | 400 VAC, 300 VDC | |
Set/Reset Time | 8 ms/8 ms |