ADAM-4011

1-ch Thermocouple Input Module
  • Input type: Thermocouple, mV, V or mA
  • Isolation voltage: 3000 VDC
  • Watchdog Timer

 

Certifications
Class 1 Div 2
Indent
Get Quote

Introduction

Analog input modules use a microprocessor-controlled integrating A/D converter to convert sensor voltage, current, thermocouple, or RTD signals into digital data. The digital data is then translated into either engineering units, twos complement hexadecimal format or percentage of full-scale range (FSR)according to the module ’s configuration. When prompted by the host computer, the data is sent through a standard RS-485 interface. The Analog Input Modules offer signal conditioning, A/D conversion, ranging, and RS-485 digital communication functions. They protect your equipment from ground loops and power surges by providing opto-isolation of the A/D input and transformer based isolation up to 3000 V DC . (ADAM-4011 has transformer-based isolation up to 500 V DC )

Specification

Part NumberADAM-4011-D2
Analog InputBurn-out DetectionYes
Channel Independent Configuration
Current Input±20 mA
Direct Sensor InputJ, K, T, E, R , S, B
Thermocouple
Voltage Input±15 mV
±50 mV
±100 mV
± 500 mV
±1 V
±2.5 V
Analog OutputCurrent Output
Voltage Output
Digital I/ODigital Input Channel1
Digital Ouput Channel2
OtherIsolation3000 VDC